Bonjour, j’ai un multiplus II 48 5000 GX sur une phase depuis plusieurs années qui charge des batteries Pylontech avec du photovoltaïque et j’ai ajouté des solarflow de Zendure sur les deux autres phases pour optimiser un nouveau contrat à 3 tarifs (heures pleines, heures creuses et heures vertes quasi gratuites). Les solarflow de Zendure Chargent leurs batteries quand le tarif est bas et les déchargent quand le tarif est élevé. Mais j’ai un problème car le Multiplus se met à charger les…
V
We install Victron battery systems and Viessmann heat pumps every day, so you can imagine how excited we were when EEBUS integration was introduced! Today, we completed our first installation combining Viessmann and Victron with EEBUS. Getting the two systems connected was surprisingly easy. In Victron, you simply enable EEBUS, and in the ViGuide app, you scan for EEBUS devices. Viessmann discovers Venus, and Victron detects the Viessmann heat pump. However! The connection doesn’t seem to be…
V
I wonder if I can integrate a SmartShunt (next to the normal items shown like, Generator, Inverter, Battery and Solar MPPT) on my Victron color display, not as additional device (this I have done), but to show it on the graphic overview . 1 post - 1 participant Read full topic
V
There is a good document how to realize a setup with Ziehl for a Multiplus 8k/10k/15k in parallel setup: 3. Installation If you like to bypass Multiplus due to maintanance or broken hardware, there are 2 options to allow the power from grid to loads: Using 2x mechanical bypass switches (grid → loads or grid → 2x relais → loads) Add a 3-position switch to control relais K2 (1-from AUX relay, 0-off, 2-230V power). In position 2, the relay is activated. To disable AC-out, you need to switch of the…
V
As we slowly continue to make changes to improve the experience on the site, today the focus is on the other languages section. As you may be aware, back in August we started to automatically translate languages so most members can experience the site, and collaborate in their preferred language. This has been tremendously successful, not only can we see a mix of people now on common topics, we have seen a good improvement in statistics about user engagement, time to get a response and…
V
Hi. I’m wondering if I can use the load output of an MPPT 100|20 on a 48 V nominal system to switch an Orion-TR 48|12-9 DC-DC converter on and off. I don’t see any voltage requirements for the remote switch in the manual for the Orion-TR 48|12-9. I’m measuring continuity between the (+) and (-) load terminals of the MPPT 100|20 when the load is on and measuring an open circuit on the load terminals of the MPPT 100|20 when the load is off. Thanks for your help! 2 posts - 2 participants Read full…
V
Hi, Today my system is in a grid loss event thus the victron system goes in emergency mode. All loads are properly serviced from the battery and pv is stored in the battery. So far so good. However, I also have a schedule at 22:02 to load the battery to 50% in 5:50 hours. Still with a SOC of 69% and coming at around 22:00 the system hard shuts down without error or anything in the logs or VRM. All three multiplusses are off. Since the SOC is way above the threshold of 50% no charging should…
V
Hello I got a problem with the installation of node-red modules. When I try to install a new module in node-red, it takes to long to install and after 2 minutes the connection with the VRM is lost, the cerbo is blocking and after 4-5 minutes the cerbo is rebooting. I update already all the software to the last version, without any success. I tried already to install node-red modules via the local way, so without VRM, this gives me the same problems. Any suggestions how I can solve this problem?…
V
I found a recent thread about the Shelly Pill: https://community.victronenergy.com/t/how-to-use-data-from-shelly-pill-with-attached-temperature-sensor-in-vrm-dashboard/63241 But It wasn’t clear if the Pill can easily be used with its Wifi connection to VenusOS. The Pill is a tiny and affordable way to get temperature values into Venus. I wasn’t sure if I could use it connected via WiFi to control diversion loads or integrate into Opportunity Loads (OL) in Node Red. However it does work, and I…
V
Hallo, Akku TAB L5.1 hat 16s LiFePo. Kann anderer Akku mit 16s LiFePo und identen Spannungseinstellungen an den Lynx dazu gehängt werden oder muss es identer Akku sein ? 5 posts - 3 participants Read full topic
V
A bad connection appeared after 18 months of use and 1 of the MC4 connectors of the MPPT is damaged after the connection started to melt. Probably a bad crimp? Although it was found working in order and within normal temperature under load after initial installation. Staubli connectors where used. I also wonder is the melting was quite high up if it was not on the MPPT side where the issue is. Can I order this part somewhere and fix it myself? Or only via a certified retailer or via Victron?…
V
So I want to use my Inverter appropriately. I do not understand why they have on-and-off, charger only and Inverter only. The “off” one is easy to understand. I need explanations for the other 3. 19 posts - 3 participants Read full topic
V
Hello Everyone, Nice to be here. I haven’t been on forums since the 2010s, it’s a nice feeling and from what i have read so far, a nice community too. I would like to introduce you a situation which I encounter since my PV system was installed (more than 1 month ago). First, my system main components: one MultiPlus-II 48/10000/140-100 inverter; 3x LiFePo4 Battery 51,2 V/100Ah NG; 3 SmartSolar MPPT 250/100 -TR Ve Can 26x Canadian Solar 460 W My connection to the Grid is ensured through a 150 m…
V
hallo, heute musste ich mich einmal intensiver mit einem meiner 3-phasen-system mit mp2 befassen, weil es sich sehr merkwuerdig verhalten hat! also habe ich zuerst einmal die config ueber das vrm heruntergeladen und dabei folgendes festgestellt: mp2 1 mp2 2 mp2 3 ups an an an aes aus an an erdungsr. aus an an ich habe danach erst einmal die ups-funktion deaktiviert und an alle gesendet (ueber veconfig und mk2) und ueber das vrm kontrolliert, keine aenderung! jetzt habe ich ueber den mk2 den…
V
Hallo zusammen, ich habe einen Batteriespeicher mit 35 kWh und betreibe aktuell einen Victron MultiPlus-II 48/5000/70-50 auf einer Phase. Im Herbst, Winter und Frühjahr reicht dessen Ladeleistung während der verfügbaren PV-Überschusszeiten teilweise nicht aus, um den Speicher vollzuladen. Insgesamt habe ich drei MultiPlus, die ich auch im Dreiphasenverbund betreiben könnte. Die zusätzliche Entladeleistung benötige ich allerdings nicht. Mir geht es ausschließlich darum, bei entsprechendem…
V
We’ve started seeing a new error on our builds that we haven’t encountered before: “Please set the VE.Can to a free number VE.Can interface - vecan0.” Our current setup has a Wakespeed WS500 connected to VE.Can port 1, with a Victron terminator at the Cerbo GX and a Wakespeed terminator at the WS500. When I check the VE.Can port 1 (VE.Can 0) settings, I see TX errors and error passive/bus warning errors. These error counts increase whenever I turn off the van’s ignition. The WS500 is…
V
Hi All, I have just had a new victron system installed on my narrow boat - Cerbro GX, Orion Smart, SmartShunt, Smart Solar, SuperPack NG. The smart shunt isn’t showing the correct state of charge - it often shows 100% charge when the SuperPack NG shows around 20%. I think the electrician who installed it has wired it up wrong. He has connected the negative of my starter battery to the negative of the SuperPack NG which in turn is connected to the smart shunt. This doesn’t seem to be correct…
V
I look after a site which has 3 Victron Quattro 48/15000/200-100/100 230V in 3 phase config It is an off grid installation I randomly get an error on all 3 at exactly same time:- Temperature L1’ on ‘VE.Bus System [276] Temperature L2’ on ‘VE.Bus System [276] Temperature L3’ on ‘VE.Bus System [276] Then instantly get:- Temperature L1’ cleared on ‘VE.Bus System [276] Temperature L2’ cleared on ‘VE.Bus System [276] Temperature L3’ cleared on 'VE.Bus System [276] The error times and cleared time…
V
Hi Community, We need some advice for our out-of-balance Lifepo4 battery. Our solar system was not checked lately, then we realized when we looked at it, that it went up til even 14.62V (!) sometime during September month. But in general each day was way over than 14.2V. Usually it was around 14.33V. Then we started to balance it to set the absorbtion voltage down to 13.8V, kept it there for 2 weeks (looked okay), then increased to 13.85V for a week (worked okay), then to 13.9V for few days,…
V
Bonjour à tous, Je suis en train de faire évoluer mon installation PV: Je viens de passer commande d’un nouveau multiplus 2 en 15kva pour alimenter entièrement ma maison. le PDL est en 12kva pour le moment, et le multiplus a été dimensionné pour supporter les consommations de ma maison, qui, peuvent atteindre 10kw en simultanée (PAC, voiture électrique, piscine , jacuzzi, clim en été, etc… Dessus, j’ai deux packs de batteries EEL avec chacune 16 cellules ehe MB31. les champs de panneaux sont…
V
Hallo zusammen, Ich möchte den Shelly im Node Red Dashoard einbinden und schalten. Ich bin Anfänger und bekomme es nicht hin. Kann mir jemand sagen wie ich das machen kann. Dieses habe ich schon im Dashboard. 1 post - 1 participant Read full topic
V
Hi, I have a new cargo trailer with a 48V battery that runs the cargo lights and other small loads. Should I add a separate 12V battery for equipment that can’t run on 48V, or install an Orion DC-DC charger/converter? I’m concerned about efficiency loss with the Orion. Adding a 12V battery would also mean installing a separate solar charging circuit, though I have plenty of room on the trailer roof. I’m trying to keep costs down, but I also like the idea of having a backup 12V battery if…
V
How do i configure my system for grid failure backup? 2x Multis, 6x Pylontec US5000, Solar MPPT, heat pump, Venus GX. 4 posts - 4 participants Read full topic
V
have EVCS with firmware v2.09/5.2 connected to Cerbo GX, 3*Multiplus II 48/3000, 60kWh PV battery, 20kWp PV modules, BYD Dolphin Surf. EVCS configuration: mode = manual, current = 6A. location = acOut start charging at backup battery SoC: 90% stop charging at backup battery SoC if off grid: 85% Allow battery/grid power for auto mode: enabled Allow low excess solar power for auto mode: enabled it is midnight (no PW power), PV battery is at 83%. I click “start charging” and EVCS starts to draw…
V
I am planning to setup the inverter and the charger (for refresh battery) in a truck. I wonder if we can combine the charger and the inverter by using the multiplus instead. Since we don’t have the secondary battery, what should be the best way to join the DC output of the multiplus to the car electrical system? If I understand correctly both inverter and charger can connect directly to the car electrical system, but multiplus cannot. 2 posts - 2 participants Read full topic
V
Ciao a tutti! Vorrei potenziare la mia barca con un impianto solare che carica le batterie, ad oggi monta 2 batteria al Piombo da 80ah, 1 per il motore e una per i servizi, tra le due batterie c’è un ponte a diodi Ho un caricabatterie da 220v che è collegato alla batteria servizi, quindi non mi carica quella Motore quando sono in banchina Qualcuno mi aiuta su cosa montare per ricaricare 2 batterie con il fotovoltaico che installerò sul capolino della barca? Grazie a tutti Riccardo 2 posts - 2…
V
I have some issues with Shelly 1 Gen 4 devices that just disappear from the VRM and Cerbo. They are being used as 12v smart switches. Latest version have done it over multiple versions 20260923-075739/2.0.1-ge1a198b Cerbo 3.85 but has similar issues going back to 3.70 which were supported to have been fixed. All devices have static IP address and reserved in router, eco mode is off, they respond from the Shelly app and work as expected but just disappear from anything victron. Any suggestions,…
V
Hi, I’ve successfully connected a bilge pump and high level flow switch (via an opto isolator) to my Cerbo. I’m able to set them up as devices and see their state on the Cerbo’s display. What I’d like to be able to do it track the pump’s daily run times, and number of cycles plus send an alert if the pump has run continuously for more that a configurable time period. I’ve built (with a bit of AI help) a NodeRed flow that exposes that data to SignalK quite successfully. I’ve also posted it back…
V
Hi, We have 3 × MultiPlus-II 6k5 units in parallel on a single-phase grid. It’s a new installation, and we’re loading on AC-Out1 with roughly 8 kW. The fans on all three units are running, all at the same level, so the load sharing seems fine. What we notice on the Cerbo is that the “load indicator” is only shown based on the capacity of one inverter (going into orange color). The “inverter” LEDs on the units are blinking/toggling in sync. Does anyone have an idea what this could be? The Cerbo…
V
Hi I don’t know how but i managed to lose that small black plastic cover for cables. It magically disappeared. I turned whole room upside down and I couldn’t find it. Is there any way I can purchase it from Victron support or anywhere in that matter? … I do have legit device with serial no I can present to them Thanks n advance 2 posts - 2 participants Read full topic