I have: Solis S6-EA1P5K-L AC battery inverter Dyness DL5 batteries Solis PV inverter(s) If I install a Victron MultiPlus-II, will the Solis S6-EA1P5K-L continue to operate and manage the Dyness batteries during a grid outage when powered from the Victron island microgrid? 1 post - 1 participant Read full topic
V
Bonjour, Je souhaiterais réaliser une installation solaire utilisant deux MPPT Victron de type 250/60-Tr, chacun associé à une chaîne PV dont la tension de circuit ouvert est de l’ordre de 230V max. J’ai compris que pour être aux normes, il faut alors utiliser un CPI afin de détecter et prévenir les dégâts en cas de défaut d’isolation sur un (ou plus) conducteur de/des chaînes PV. Mon problème est le suivant: je ne sais pas s’il faut utiliser: 2 CPI, (1 par MPPT), au niveau de l’entrée PV des…
V
Hi, I have an off-grid MultiPlus-II 48/5000 with Cerbo GX, DVCC and two Skanbatt 51.2 V/100 Ah LiFePO4 batteries. Generator is a Hyundai DHY8600SE 230 V/50 Hz AVR diesel generator. The issue is intermittent generator acceptance. The Multi sometimes: accepts generator AC normally, starts charging, then drops AC/charging, but generator continues running and its breaker remains on, and the Multi may then remain disconnected for 5–10+ minutes. Sometimes it eventually reconnects by itself and…
V
My MP II 6K5 don’t see the grid even circuit breaker is up and the power arrive to the inverter.How can i solve this?Firmware version is 570.TIA 9 posts - 3 participants Read full topic
V
Is it possible to modify the correction table used to display the correct power output? My primary goal is to adjust two specific values. The readings differ depending on whether the system is operating in off-grid mode or connected to the grid—likely due to a difference in impedance. I currently retrieve the generated kW figures (for reporting to my employer) using Node-RED, which works fine; however, the accounting department also requires a photograph of the external electricity meter. This…
V
Hi, Complete newbie here. Would anyone be able to sanity check my wiring diagram please? I have a dual battery setup at the front of car with starter, Aux, Solar, MPPT and DC to DC. Some USB ports and camp lighting at front. Then cabling to back to Fridge and more USB ports. I think I’m missing a ground after smartshunt but not sure where to place. Thankyou link below: https://usewireframe.com/view/d3edb6f9e64b49aaae90f1701118d40d 3 posts - 2 participants Read full topic
V
i have a 15kva MP2, ac coupled with 8 x PP4851managed batteries. Over the last 2 days the inverter has shut down and restarted (276 low voltage), Once at night and once during the day. There is no low voltage, does this indicate a BMS issue? 3 posts - 3 participants Read full topic
V
This move to 2FA has been all very well, but this in the only one in dozens of implementations that has let me down and locked me out. Thankfully the login via link works, but I want to disable this now. I’d rather wait till proper passkey support is there, I am sick of maintaining 100 different MFA tokens. However, I don’t see any way to actually remove or disable the now broken 2FA that was setup. 3 posts - 2 participants Read full topic
V
Hello all, I cannot log-in on local network to my new version (Mk3) Cerbo GX as the password (which I have not set) is not recognised. I have tried all of the standard default password variations with no luck. I can access via VRM remotely with no problem, any ideas? I have not ever had this problem with earlier Cerbo’s 21 posts - 5 participants Read full topic
V
I have recently installed the following: 3 x Multiplus 2 6k5 Connected in a 3 phase setup and also used a Cerbo GX as the controller. And a 16Kwh battery with JKBMS I was now planning to actually start using the system and purchased a MK3-USB-C interface in order to communicate with the multi plusses. The bus connection is done as shown in the manual, L1 => L2 => L3 and normally then the cerbo, however i disconnect the cerbo and connect that UTP to the MK3-USB-C. first of all i started with VE…
V
New DESS user here. Just wondering a few things; 1. Is it possible to force getting the spot prices sooner, when we know they are available? 2. How much time will DESS typically take to calculate tomorrow’s strategy from when it gets the prices? What should we expect? 3. If we change the min SOC, how much time will DESS typically take to recalculate that? 4. Also, just curious, are DESS calculations done in VRM, GX device or in a MP assistant? Many thanks 12 posts - 5 participants Read full…
V
Hi all, My three-phase system occasionally drops the AC output for a few seconds while the grid itself stays up. As far as I can tell, one Multi RS loses contact with the other two, all three shut down and then restart. My NAS on AC-out logs the outages, but VRM shows almost nothing. System 3× Multi RS Smart 48/6000/100, three-phase, firmware v1.31 (all three) Cerbo GX MK2, Venus OS v3.80 (Large); the outages below happened on v3.79 64 kWh LiFePO4 battery with CAN-bus BMS (shown as “Generic…
V
Hallo zusammen, Mir ist mein Landanschluss abhanden gekommen, woraufhin sich die Verbrauchsbatterien in den Ruhestand verabschiedet haben. Aber auch die beiden Starterbatterien für Backbord und Steuerbord sind nur noch so bei 35 % Leistung. Müssen also auch erneuert werden. Aktuell also ein System aus 2 Starter und 2 Verbraucherbatterien. Letztere sind parallel geschaltet. Dazu gibt es an Bord ein Ladegerät Quick SBC 500 welches bisher die 3 Bänke geladen hat. Meine erste Maßnahme war jetzt 4…
V
Moin liebe Community! Habe meinen Ekrano letzte Woche von Version 3.80 auf 3.85 geupdatet. Dabei ist mir aufgefallen das meine PV Anlagen nur noch an der Position vom AC1 IN angezeigt werden. Normal sollte eine am AC out angezeigt werden. In der App und im VRM ist alles auch so nur am Ekrano selber nicht. Hat jemand eine Idee oder das selbe Problem? Gruß in die Runde 7 posts - 3 participants Read full topic
V
Hi there, First, I have been using the VRM for a while now & it is absolutely grand, it’s been a gamechanger for our offgrid setup. Thankyou However, similarly to this topic here Introducing the VRM AI Assistant I need to be able to turn this off. the big difference since this topic is: there is now one of these on the front dashboard & it (and its friend in the Advanced view) are animated. I’m neurodivergent & I cannot concentrate with these things wriggling about in the corner like a child…
V
Greetings! I’m looking for some help/guidance on my planned system: 4 x 300ah 12.8v lifepo4 batteries, connected parallel, then parallel to: 1 x Lynx Class T Power in (4/0 wire), then Lynx Shunt, then Lynx Distributor, connected to: Victron Multiplex 12v 4000va 160-50 2x120 Question: re Isolation/Cutoff switches for batteries…should I bother to try to put them in? (cable run from batteries to Power in is maybe 3 ft.), or just utilize the class T fuses to isolate the batteries? Also, is the…
V
Does the VM-3P75CT & VM-3P5A log VA and PF in VRM as time-series data? I’m working with a customer that runs a summer camp off-grid on three phase diesel generators. They have no energy meters with logging and they can’t tell me what their peak and average loads and daily energy needs are since they don’t log the data. The camp uses three phase commercial equipment in the kitchen (i.e. mixers, refrigeration) and three phase septic lift pumps and well water pumps so I want to log VA and PF along…
V
Passt sehr gut zu Victron-Anlagen: ortsnetz-auslastung.de Ortsnetz-Auslastung – Spannungen im Stromnetz Karte mit aktuellen und historischen Spannungsmessungen aus Ortsnetzen in Deutschland, Österreich und der Schweiz. Daten per Script hochladen und mitmachen. Ihr findet die Scripte und Intergrationen unter github > Github > datenerfassung-ortsnetz-auslastung 5 posts - 3 participants Read full topic
V
As the days get shorter and colder, I have been thinking about what to check on our home solar and battery setup before winter really sets in. I usually look over the panels for leaves and dirt, and check that the battery area stays dry and well ventilated. I also like to review the recent charging patterns to see whether shorter days are changing how much charge is available in the evening. Small habits, like clearing debris and checking connections visually, feel more useful than waiting for…
V
Victron Solar & Battery System – Summary Inverter / Charger 1 × Victron MultiPlus-II 48/8000/110-100 8 kVA nominal inverter capacity. Approximately 6.4 kW continuous usable AC output. Operating with Victron ESS (Energy Storage System) and Dynamic ESS / Trade mode. Solar PV System Approximately 15.5 kWp total solar capacity. Includes 21 additional solar panels installed as an expansion. Solar generation feeds the battery storage and supplies the property, with surplus exported to the grid.…
V
Sind de laatse update is de ESS software verdwenen van dit toestel. Het werkte nochtans goed op DESS tot nu toe. Kan dit van op afstand opgelost worden ? 4 posts - 3 participants Read full topic
V
Hallo in die Runde, Ich stehe heute mit einer Frage betreffend eines Solar Ladereglers vor Euch folgendes System, ich betreibe 3 Stk. Solarpanele 100W/18V/5,56A in Serie über einen Trennschalter an einem Smartsolar MPPT 100/30 am Abgang mit 16mm2 und SI 40A an die Plusbusschiene weiter zur Batterie. Das selbe System ein zweites Mal auch an die Plusbusschiene, an der plusbusschiene hängt auch noch über Sicherungen ein Victron IP43 smart ladegerät sowie ein Victron Ladebooster, dieses System hat…
V
Ich bekomme bei Konfigsichtungen auf meinen MP2 immer die Ansage, dass der ESS Assistent upgedatet werden kann. Der Versuch, im Changelog Versionsinformationen zu bekommen, schlug fehl. Der aktuelle ESS-Assistent ist 0190, Laut Changelog ist 018E (Sept. 2025) aktuell. Was wurde geändert? 1 post - 1 participant Read full topic
V
Hello all, I have a system with a cerbo gx, smartshunt 1000A, orion XS 50A charger, 4 100Ah NG lithium batteries, a VE.bus BMS NG, and a 150/100 mppt. I noticed that in the device information page for the orion that it says “network status: standalone”. Is this normal? Considering that everything is connected through the cerbo and dvcc is enabled I find it strange for this to be the case. Even when active and charging it remains at standalone. Does this need to be connected to the smartshunt…
V
My BMV700 often shows 100% charged when I had expected it to take longer to charge. Its installed on a boat, and for example we can discharge the 360AH bank by 100AH then perhaps charge at 50amps. So I would expect 2 hours till fully charged (assuming constant current) but it often indicates 100% after about 1 hour. Is there a setting on the BMV700 that I should check, I am fairly sure I have the capacity set to 360AH but will check. 8 posts - 4 participants Read full topic
V
Ich finde den Beitrag zum VRM-Update nicht mehr, in dem es um die Probleme beim Aufruf der Remote Konsole aus der Web-VRM-Version ging. Mir fällt es in den letzten Tagen vermehrt wieder auf, dass ich die VRM Seite nach Tabwechsel oder Standby aktualisieren muss bevor ich die Remote Konsole aufrufen kann. Ausserdem haben trotz aktivem Echtzeitstatus die Opportunity Loads Schalter gelegentlich den falschen Status oder werden nicht alle angezeigt. 6 posts - 4 participants Read full topic
V
Hello, We have an ESS system that is discharging the battery into the grid. It ignores the grid setpoint, the feed-in limit and the minimum SOC. I’d appreciate your help diagnosing it. SYSTEM 9x Quattro 48/10000/140-2x100 120V, 3 per phase, 208/120V 3-phase Phase masters: L1 HQ2243RK9HV, L2 HQ2146XUMEZ, L3 HQ2133RUDYN Cerbo GX, firmware 3.85, image type Normal (no Node-RED) Grid on AC-in 2; generator on AC-in 1 BSLBATT LFP bank (~8,000 Ah) with BMS on the Cerbo (CVL 56.0 V); DVCC forced on, max…
V
2 - Quattro 5000 in split phase with the grid input current set to 20A. To comply with local reg’s, I want to reduce that setting down to 16A. Using VE Bus system configurator and the Mk3 dongle connected to an unused port on one of the Quattro’s. Within a minute or two of connecting the dongle & opening the App, both Quattro’s shut down and causes me headaches. Is this normal behaviour?, and if so what are the next steps in setting the grid input max level? 5 posts - 4 participants Read full…
V
I have created a S2 resource (heat pump) for using as opportunity load, that turned up in the list of opportunity loads in the console. Later, I created a Virtual Device, representing a water pump AC-load. After creating this, instead of the S2 resource, the water pump turned up in the opportunity load list. Removing the water pump virtual device, the S2 resource is again back in the opportunity load list. Could it be that the S2 resource (heat pump) and the Virtual Load (water pump) get the…