Can someone at victron remove bogus data from vrm?
I have a site where bogus data was stored in the beginning. Can someone remove this? Site ID 1050069 2 posts - 1 participant Read full topic

Posts from every feed QUEST has found across the web — blogs, news, podcasts, channels and more.
I have a site where bogus data was stored in the beginning. Can someone remove this? Site ID 1050069 2 posts - 1 participant Read full topic

I have a site with an enphase system where I use Shelly Ogemray Smart relay 25A. At night the enphase system uses 3 watts which Venus reports as solar generated power which is incorrect. Positive watt values of the shelly should be ignored. 1 post - 1 participant Read full topic

Hello all, I ported a sweet python app in Go that scan BLE temperature and humidity devices, convertit to RUUVI payload and “ship” it to the CerboGX DBUS so it can be used/displayed. I was able to confirm it working with my Govee sensors… I’d love if people with other kind of sensors could test it… Please find code and docs at https://github.com/prune998/thermobeacon-ble-go/tree/main Check the release page to download the right version and docs specific to Cerbo at…
Hello everyone, I suspect this is done routinely but I couldn’t find the right posts through search. The objective is to store energy in a reserve battery bank chargeable via solar only to use it at night instead of drawing AC power from the unreliable grid for my main separate system. This is the thinking: create a reserve solar system that has its own PV, MPPT, battery bank, and inverter. I’m thinking of the Phoenix Smart 3k. Use the secondary inverter only as AC In 2 to a fully functioning…
Hallo Gemeinde Ich habe eine Inselanlage. Bestehend aus: Pylontech Akkus, Smart Solar MPPT und einen MP2 48/5000. Gesteuert wird das alles über Cerbo GX. Nun möchte ich die Anlage erweitern. Ich brauche zwei unabhängige Stromkreise (Wohnung und Werkstadt). Die beiden werden Naturgemäß unterschiedlichst belastet und die Werkstadt soll bei nichtbenutzung abschaltbar sein. Kann ich das mit einem Zweiten MP2, mit nichtidentischer PN (hätte ich da) realisieren? Und wenn ja… Wie? Danke im Vorraus…
I have a 5kva multiplus easy solar with 4kw solar and 10kwh batteries. I have a backup generator connected to it. This is at our original offgrid house and we then added another house with 2 x 5kva Quatros in parralel with 8kwh battery without its own solar. The house with solarpanels provide a grid connection to the second house. I set the grid current limit on the second house to 6 amp and the batteries are charged at that rate. When a load is drawn on the quatros it exceeds the 6 amps and…
Hallo in die Runde, beim Solarsense 750 mit der aktuellen Firmware ist mir aufgefallen, dass er öfter den Tagesertrag am Tag verliert, bzw auf null resetet. Wie der Tagesertrag untertägige zurück springt ist auch in VRM gut zusehen . In Victron Connect ist es das gleiche Verhalten Der Solarsense hängt über den Shelly BLE extender am GX Gerät Irgend jemand eine Idee dazu? 13 posts - 3 participants Read full topic

Bonjour, Qui connaitrait la section max des conducteurs que l’on peut câbler sur les contacteurs du boîtier Anti Islanding Box (avec le ZIEHL UFR1001E à l’intérieur) ? Pas de documentation sur ce boîtier … Merci d’avance 7 posts - 3 participants Read full topic
When adding devices like shelly or pv inverters an ip has to be specified but it’s not possible to use a hostname. This causes the need of fixed ip addresses. Normally with advanced users this is not a problem but with non technical users this can cause connectivity issues when they change there internet modem when they switch internet provider. Using mdns names would solve this issue. The device get new ips in a new range and will be found by mdns. 3 posts - 2 participants Read full topic
Hello, I would particularly appreciate a technical response from Victron regarding the following behavior of my charge controller. I would like to know whether this is normal operation or a fault that should be addressed under warranty. I have four Victron SmartSolar charge controllers installed: 3× MPPT 250/85 – in operation for approximately 1 year 1× MPPT 250/100 – in operation for approximately 6 months All four controllers are running on firmware version 3.18 and are connected via VE.Can.…
Buenos días, me encuentro con que no puedo conectar con mi Compact Multiplus 12/800/35 (nunca antes lo conecté). VE.Configure3 versión 90.04.248 me detecta el MK3 USB pero me devuelve el siguiente error: MK3 detected (VE.Bus devices only) En las pegatinas del equipo me nuestra estos datos *CMU 012801000* / *06430100061* Y en el chip tengo este número que debe ser el firmware 1803133.VFF Debe tener unos 20 años, pero está bien conservado y pretendo cambiar la programación para el uso de baterías…
Ik ervaar dat er weinig aandacht voor digital security in kader van gebruik van o.a. Cerbo en Internet en IOT in het algemeenheid, Zie de 3e debacle rond de FrigoGate en overige IOT devices. Maar ook dat er weinig reacties zijn om Cerbo in de kader van Shelly integratie gebruik te laten maken van Shelly Devices met een wachtwoord, in plaats van exposed shelly’s Ik kom ook implementaties tegen waarbij de Cerbo en Shelly zonder wachtwoord in het zelfde netwerk-segment als gewone gebruikers. Of…
I am getting confused by the different temperature readings. Since 2 months I have 2 Victron LifePO4 NG 25.6 V 300 Ah batteries on my yacht. I keep a close eye on cell voltage, balance and the temperature. Yesterday I had measurement of 46 degrees showing on the dashboard of VRM and on the Remote Console. That scared me. When I checked the the detailed temperature of the cells, it said it was only 14 degrees. So now I am confused. See screenshots. Where is the measurement of 46 degrees coming…

Buongiorno a tutti, ho acquistato da qualche giorno un nuovo cerbo mk3 . Dopo varie configurazioni, mi sono reso conto di doverlo resettare. Tutti i metodi che ho trovato riguardano l’istallazione del firmware tramite interfaccia grafica. Vorrei invece eseguire un Factory reset tramite boot da USb ma tutti i tentativi falliscono. Qualcuno può indicarmi la corretta procedura ? 5 posts - 3 participants Read full topic
Hola Tengo dos Multiplus 5000/48/70 funcionando en paralelo con cerbo y un grupo electrógeno de 7kva, tengo picos de potencia al arrancar motores de poco más de 10kw y un consumo de trabajo de unos 5kw, cuando arranca el grupo electrógeno, la mayoría de las veces se vuelve loco y se acelera a tope, yo lo tengo limitado en intensidad o en VE CONFIGURE o en la propia pantalla GX, o lo paro el grupo o termina cortando por sobre potencia, además tenemos dos iguales, uno de reserva y con los dos…
My BMS12/200 shuts down intermittently. Batteries are fully charged by solar. When I turn on house power, it shuts off about every 15-30 sec. After an hour or so it stabilizes. In the app, the System On switch shows OFF and sometimes the System ATD (allow to discharge) goes OFF. But those are fleeting, and it starts up again immediately. But chartplotter, autopilot, and Radio all take time to recover, and often shut down again before fully functional. Checked all wiring, nothing loose, and no…
The system consists of the following components: 3x Quattros 15000VA 48V 230V on 3phase configuration 2x SmartSolar mppt 250/100 connected via ve.direct 1x Fronius Verto 33.3kW 1x CCGX 6x 16.6kWh poweroad Tervol L16 1x 3 Phase 20kVA generator The Quattros will form a 400/230 V, 50 Hz island network. The PV Inverter Support Assistant will regulate the Fronius through frequency shifting during inverter operation, with the Fronius configured for compatible MicroGrid operation (MG50 grid code). As…
Hi for quite some time now I regularly get low battery ALERTS notifications from VRM while my battery is completely fine with pleny of chenergie. The CLEAR message always follows a few seconds after that. The system is setup with a min charge setting of 11%. See below email I received while the battery is at around 51%. From: VRM Notifier bounces@victronenergy.com Subject: ALERT - ‘Hweg’: ‘Low battery’ on ‘VE.Bus System [276]’ Date: Wed, 4 Nov 2026 18:48:49 +0100 (CET) To: marcel@emol.nl VE.Bus…

Hi all, I would love to share with you the latest changes that were just added to production VRM: The Dynamic ESS chart on the dashboard now only loads once you scroll down to it, so the rest of your dashboard opens faster. On mobile devices, the Dynamic ESS chart now shows the time axis in 2-hour steps, just like the EV Charger chart. The labels no longer crowd together, which makes the chart much easier to read on a small screen. The AI assistant no longer jumps to the bottom of the chat…

I have a Quattro II with Generator connected on AC1 and Shore Power on AC2 and a Cerbo GX along with a smart shunt, when used with Shore Power, it shows up in the GUI Brief page but when the Generator is being used it does not show up. Is there a way to make that appear? 4 posts - 2 participants Read full topic

Do you think Alarm and Warning Notifications could be improved? Here are a few ideas. better use of color and icons for consistency in VRM and Venus OS GUIv2 sort order of most recent alarms and warnings on GUIv2 Actual values that triggered alarms and warnings (I can’t remember what the thresholds were set to, so I would have to go digging in configuration in the middle of the night, so either tell me the value or give me the threshold and units eg Overload happens when > 1000W or 1200VA). Was…

Hello everyone, I’m building a portable 24 V off-grid power system for a small mobile pizza kitchen, using the following components: Victron Phoenix Inverter 24/1200 VE.Direct SCHUKO (PIN242121200) 24 V LiFePO4 battery in a separate removable enclosure 30 mA RCD protecting two additional Schuko outlets Wooden enclosure containing the inverter and AC distribution No shore power or external AC input – the Phoenix is the only 230 V source The system will be used in two different configurations:…
New installation with bank of three E/Bick batteries (48V, 3x13KWH) and RS 450/200 Solar Charger: Initial startup went fine with the bank at ~95% SOC. The battery has a pre-charge function that brings the buss up to ~48V before closing the internal contactors. After running normally for a couple days, the bank was at 100% SOC and the system was shut down for some wiring work. The bank then failed to re-start. The bank would fault out during pre-charge and trip out. Pulling the battery fuse for…
I’m designing an electrical system for my small overland vehicle. Currently, I’m considering two options: A cheaper option with a non-Victron battery (built-in BMS). The non-Victron battery has a built-in heater. A more expensive option with a Victron battery and an external BMS. The Victron NG 12.8V, 200Ah battery does not have a built-in heater. Any advice on how to address this would be appreciated. Being able to charge the battery at temperatures below 0°C would be helpful, as I plan to…

Hi I am new to the community and solar set ups. I have 4 x 240w 12v Isc 10.98a solar panels that i want to set up as 2 strings in parallel. Each string with a 40a dc breaker. I will be using 6mm cables to a Victron 150/85a charge controller. I also have a Renogy 3000W inverter and 4*100ah 12.8v lifepo4 1280wh batteries. I was advised to set the batteries up in series+parallel. I am confused with the cables I need from charge controller-> battery->inverter. I also know I need a battery isolator…
Ik heb een Renault 5 e-tech en op dit moment nog een 1 fase 16A laadpaal. Er loopt vanaf de meterkast naar de garage een 4x 2,5mm2 kabel met aard-litze van ongeveer 30 meter lang. ik heb daarvan 2x2 aders samengevoegd en zo minder spanningsval kunnen bewerkstelligen voor laden op 1x 16A. Vanaf die kabel in de garage gaat nog ongeveer 15 meter 3x 4mm2 naar de laadpaal. De renault 5 is gevoelig voor onderspanning en ik heb nu al vaak dat ik in de avond in de garage 208v zie op de homewizzard kwh…
Hello, Just added my Shelly PRO3EM with Cerbo GX 3.85. Could you add an “EV Charger” category for shelly CT? I think this can be helpful for DESS forecast… Thanks. Kind regards, Julien 1 post - 1 participant Read full topic
Ik ga de MB31 cellen gebruiken maar deze zijn te verkrijgen in enkel en dual stud uitvoering. Mijn voorkeur gaat uit naar dual stud (2x6mm terminal) maar deze zijn zeer slecht verkrijgbaar, vooral wanneer je de hoge kwaliteit wil (en die wil ik). Heeft iemand hier ervaring mee, met de enkele of de dubbele terminal? De dubbele lijkt robuuster en betrouwbaarder maar de single is goed te verkrijgen. 23 posts - 8 participants Read full topic
I want to use just the clock in the cerbo puerly as a relay on off timer for relay 2 on the cerbo, (relay one is already in use) I want relay two to close at midnight and open at 5am regardless of any conditions, only the clock needs to time that relay. I have node red installed, but cant figure out which nodes to choose from the left and how to wire them, or if this is even possible. Can anyone please help and possibly draw me a node flow diagram? 8 posts - 4 participants Read full topic
Hi, I only found the oldest version 1.61 in Victron Professional firmware section. Is there a way/link to get older versions? 5 posts - 2 participants Read full topic